Power Station Circulating Water System Assessment

Flowserve
Flowserve Power Station Circulating Water System Assessment (2)

Power Station Circulating Water System Assessment

By: Flowserve

The Challenge: A multi-unit power station in North America was concerned that the circulating water system serving two of its units was operating at low efficiency. Flow distribution inequality and the resultant increase in unit condenser backpressure were suspected. Plant engineers also speculated that limited condenser cooling flow during periods of low river level resulted in derated unit performance.

The Solution: Flowserve performed a thorough hydraulic study of the circulating water system for Units 1 and 2. Study findings confirmed low-flow conditions were impacting system performance. Supported by detailed hydraulic modeling and analysis, Flowserve recommended retrofitting two circulating water pump trains with higher-speed motors. This would increase water flow to the condensers and reduce condenser backpressure.

A multi-unit power station located on a large river was concerned that the circulating water system supplying Units 1 and 2 was operating inefficiently. Flow distribution inequality, increased condenser backpressure and reduced flow during periods of low river level were suspected. Flowserve was engaged to analyze the system and recommend corrective actions.

As a first step, Flowserve conducted an on-site assessment of the cross-connected circulating water system supplying Units 1 and 2. The system consisted of four vertical pumps operating in parallel. These pumps provide water to the condensers for both Units 1 and 2. They also supply the Unit 1 and 2 condensate coolers, the jacket water coolers and the raw water pumps.

Flowserve Power Station Circulating Water System Assessment (1)

Simplified diagram of cross-connected circulating water system supplying Units 1 and 2

Flowserve engineers determined that noninvasive flow monitoring instrumentation and state-of-the-art wireless technology were best suited for the specific configuration and layout of the system. After installing the instrumentation, Flowserve engineers collected and compiled high-resolution data during various field test scenarios.

A comprehensive hydraulic study was then performed. A hydraulic model of the circulating water system was developed and validated by actual field data. This high-resolution model was then used to evaluate system response to multiple variables, including:

  • Pump hydraulic designs
  • Motor/pump speeds
  • Number of pumps in operation
  • Plant power levels
  • Condenser discharge valve position
  • Condenser cleanliness
  • River levels
  • River water temperature

Recommendations:
As a result of the testing and data analysis, Flowserve confirmed:

  • Unequal distribution of flows existed throughout the system
    • Flow to the Unit 1 condenser was greater than design in all field test scenarios.
    • Flow to the Unit 2 condenser only reached design level when four pumps were in operation, a condition typically only found in the summer months when additional flow is required to compensate for the increased river temperature.
  • A significant reduction of flow to both units’ condensers occurred during periods of low river elevation.
  • Low-flow conditions did in fact cause increased condenser backpressure in both units compromising unit power generation capability.

Flowserve recommended two circulating water pump trains be retrofitted with higher speed motors to provide greater capacity during times of low river levels. The hydraulic model was used to verify that two higher-speed motors the client already owned would provide the necessary increase in pump capacity. The increase in flow provided by these new motors would mitigate the low-flow conditions and, therefore, reduce the condenser backpressure. Steam cycle efficiency would be improved, positively impacting the stations bottom line.

Flowserve also recommended the installation of cutting-edge, fixed-flow measurement instruments to increase the plant’s visibility to the amount of flow to each of the condensers. This information would enable plant personnel to track condenser efficiency and system performance.

It is anticipated that these recommendations will greatly lessen the impact on varying river levels on the station. The use of existing plant stock motors will result in large capital savings. Additionally, the increased flow should marginalize the flow inequality that is otherwise difficult to correct without undertaking major modifications to the piping.

Related Articles

Flowserve IIoT Solutions for Seals (4)

IIoT Solutions for Seals

Learn about the conditions inside mechanical seals It is often the mechanical seal performance data that is the best and earliest…

Related Whitepapers

Expansion Joint Expertise Improves Industrial Wastewater System Reliability

The majority of industries have wastewater treatment plants. Government agencies and local governments require these facilities to meet pretreatment requirements. Pretreatment rules were enacted to prevent…

How to Decrease Oil Changes with Bearing Isolators [Inforgraphic]

Learning how to decrease oil changes can be time- and money-saving. Oil life can be long if contamination is eliminated, which is easier said than…

Synchronous Machines Are The Optimal Choice For Heavy Industry

TECO-Westinghouse experience assures superior performance and reliability For over a century, Westinghouse has been the pacesetter in the design and production of electric machines for heavy…

Why FLEXXORs Are Designed Differently

J. Hilbert Anderson, President of Coupling Corporation of America, discusses some of the reasons why FLEXXORs are designed differently from all other flexible couplings, and…

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *

Join the #PumpTalk Community


By submitting this form, you are consenting to receive marketing emails from: Empowering Pumps & Equipment, 2205-C 7th Street, Tuscaloosa, AL, 35401, http://www.empoweringpumps.com. You can revoke your consent to receive emails at any time by using the SafeUnsubscribe® link, found at the bottom of every email. Emails are serviced by Constant Contact